Key Product Features
- Cost effective Safe Area Transmitters
- Low cost of ownership
- Simple installation
- Robust steel enclosure
- Configurable 4-20 mA outputs
Toxic Gases
The GMI Transmitter sensors use proven electrochemical sensor principles to detect and monitor for a selection of toxic gases in the parts per million (ppm) range and % volume oxygen. They are designed for use in non-hazardous area applications such as car park monitoring systems.
Gas sensors: CO, VOC, SO2, Cl2, NO2, NH3, NO, Freon, H2S & O2.
CO2 Gas
The GMI Transmitter sensors use proven infra-red detection principles to detect and monitor for carbon dioxide gas.
There are two standard ranges available: 0-5% Volume CO2 and 0-100% Volume CO2.
They are designed for use in non-hazardous area applications such as brewing, landfill/biogas, refrigeration.
The GMI Transmitter Sensors operate on a 3/4 wire connection and provide a linear, calibrated 4-20 mA output to allow connections to our range of fixed control panels or, alternatively, direct to existing PLC, DCS or external control systems.
The sensor and the amplifier electronics are housed in a sturdy mild steel enclosure which has built-in external mounting lugs to allow ease of fitting. The amplifier PCB has built in Zero and Span potentiometers to allow a simple and reliable calibration procedure.
|
Specification
|
Outputs
|
|
Carbon Monoxide
VOC
Sulphur Dioxide
Chlorine
Nitrogen Dioxide
Ammonia
Nitric Oxide
Freon
Hydrogen Sulphide
Oxygen
CO2
|
0-1000 ppm
50 ppm Isobutylene
0-30 ppm
0-10 ppm
0-20 ppm
0-100 ppm
0-300 ppm
0-2000 ppm
0-100 ppm
0-25% Vol.
0-5% Vol.
0-100% Vol.
|
4-20 mA Linear Sink/Source
Optional Fault Relay (30v DC@1A)
|
|
Power Supply
|
Environmental
|
|
12-24v DC
|
See Product Datasheets for Individual Gas Specifications
|
|
Physical Properties
|
|
Dimensions:
140 x 140 x 60 mm
|
Weight:
0.5 kg
|
- Brewing/Fermentation
- Bottling Plants
- Landfill/Biogas
- Steel Plants
- Refrigeration
- Combustion Processes
|